SEAT/Volkswagen AG, Plant Matorell

 

New Building of a Company waste water treatment plant


Characteristics:

  • Domestic sewage Qh = 500 m³/h BOD5 = 300 kg/d
  • Industrial sewage Qh = 270 m³/h BOD5 = 3,300 kg/d
  • Sewage goods 60,000 PE- Amount of sewage 50,000 PE

Scope of Work:

  • Draft planing
  • Elaboration of tender documents
  • Allocation
  • Supervision

Description:

The sewage of the SEAT-Plant in Matorell is separated into two canal networks. The sewage that is cleaned in the treatment plant, that belongs to the plant, goes into the receiving river. To clean the sewage the following procedures were chosen

The several partly streams of the industrial sewage are kept separate. In the treatment plant, the industrial water is hauled over a data processing system and a grit chamber. Afterwards, it is treated in a chemical-physical step. This step consists of a two-step pre-precipitation (acid/basic) and afterwards a sedimentation tank for the separation of the felling-sludge and the floating sludge. Then the common stream will be cleaned biologically in an activated sludge plant. The facility is based on carbon elimination and nitrification. The sludge is simultaneous aerobe stabilised. The drainage is disinfected with chlorine before it drains out.

Finally, in the sludge treatment a (pre-thickener) and two chamber filter presses dewater the sludge.


Client / Operator:

Volkswagen AG,
Environmental Planning
Hochring 39
D - 38440 Wolfsburg (Germany)


Contact:

Mister Mogg
Phone: ++49 - 53 61 - 97 06 79

spain

The treatment plant SEAT-Matorell

Engineering Group
Dr. Born - Dr. Ermel
Finienweg 7

D - 28832 Achim
Germany